Minimum Rating
60 KVA / 47.2 KW
Maximum Rating
60 KVA / 48 KW
Emissions/Fuel Strategy
EU3a Emissions Compliant
50 Hz Prime
60 kVA / 48 kW
50 Hz Standby
60 Hz Prime
60 kVA / 54.2 kW
60 Hz Standby
Frequency
EU3a Emissions Compliant
Speed
1500 or 1800 RPM
Voltage
127-480 Volts
50 Hz Prime Rating
60 Hz Prime Rating
50 Hz Standby Rating
Engine Specifications
Engine Model
1104D-44TG2
Bore
105 mm (4.1 in)
Stroke
127 mm (5.0 in)
Governor Type
Mechanical Actuator
Displacement
4.4 L
Compression Ratio
18.23:1
Benefits & Features
Exhaust
- Industrial, Residential, Critical Silencers
Alternator
- Permanent Magnet Generator (PMG)
- Anti-condensation heater 110 or 230 VAC
Starting/Charging
- 12V battery charger
- UL/CSA listed 120 V, 20 Amp battery charger, shock mounted and enclosed in dust proof housing
General
- CE socket box with integrated MCB and RCBO protection
- Clipsal socket box with integrated MCB and RCBO protection
- Coolant heater 110 or 230 VAC
- CE labelling (also available for BSFC)
Engine
- Air Cleaner
- Lube oil drain valve
- Engine filled with lubrication oil
- High Coolant Temperature Shutdown
- Low Oil Pressure Shutdown
Cooling
- Cooling package mounted radiator with high ambient capability
- Pusher fan with guards
- Coolant drain line with internal brass ball control valve piped to base-frame
- Low coolant level shutdown.
- 50% coolant antifreeze with corrosion inhibitor
Exhaust
- Integrated spark arresting silencer with flexible connectors, in separate compartment
Fuel
- 301L double wall fuel tank, 24 hr runtime @ 75% prime rating
- Auxiliary connections for customer supplied fuel transfer with 3 way fuel transfer system, internally mounted within the bunded area.
Alternator
- Leroy Somer
- SHUNT Excitation
- IP23 Protection
Control Panel
- PowerWizard 2.1+
Mounting
- Generator set soft mounted using captive vibration mounts
- Heavy duty steel base frame contains integral double wall fuel tank
- Provides 110% spill containment of all engine fluids
Optional Equipment
Exhaust
- Industrial, Residential, Critical Silencers
Alternator
- Permanent Magnet Generator (PMG)
- Anti-condensation heater 110 or 230 VAC
Starting/Charging
- 12V battery charger
- UL/CSA listed 120 V, 20 Amp battery charger, shock mounted and enclosed in dust proof housing
General
- CE socket box with integrated MCB and RCBO protection
- Clipsal socket box with integrated MCB and RCBO protection
- Coolant heater 110 or 230 VAC
- CE labelling (also available for BSFC)
Standard Equipment
Engine
- Air Cleaner
- Lube oil drain valve
- Engine filled with lubrication oil
- High Coolant Temperature Shutdown
- Low Oil Pressure Shutdown
Cooling
- Cooling package mounted radiator with high ambient capability
- Pusher fan with guards
- Coolant drain line with internal brass ball control valve piped to base-frame
- Low coolant level shutdown.
- 50% coolant antifreeze with corrosion inhibitor
Exhaust
- Integrated spark arresting silencer with flexible connectors, in separate compartment
Fuel
- 301L double wall fuel tank, 24 hr runtime @ 75% prime rating
- Auxiliary connections for customer supplied fuel transfer with 3 way fuel transfer system, internally mounted within the bunded area.
Alternator
- Leroy Somer
- SHUNT Excitation
- IP23 Protection
Control Panel
- PowerWizard 2.1+
Mounting
- Generator set soft mounted using captive vibration mounts
- Heavy duty steel base frame contains integral double wall fuel tank
- Provides 110% spill containment of all engine fluids