Generator Set Specifications
Minimum Rating
36.0 kVA / 36.0 kW
Maximum Rating
45.0 kVA / 45.0 kW
Emissions/Fuel Strategy
Fuel Optimised
50 Hz Prime
36.0 kVA / 36.0 kW
50 Hz Standby
40.0 kVA / 40.0 kW
60 Hz Prime
40.0 kVA / 40.0 kW
60 Hz Standby
45.0 kVA / 45.0 kW
Frequency
50 / 60 Hz
Speed
1500 or 1800 RPM
Voltage
220-240 Volts
50 Hz Prime Rating
These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours.
60 Hz Prime Rating
These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3).
50 Hz Standby Rating
Standard reference conditions 25°C (77°F) Air Inlet Temp, 100m (328 ft) A.S.L. 30% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2.
Engine Specifications
Engine Model
Perkins® 1103A-33TG1
Bore
105 mm (4.1 in)
Stroke
127 mm (5 in)
Governor Type
Mechanical
Displacement
3.3l (201.4 cu. in)
Compression Ratio
17.25:1
FG Wilson Diesel Engine
Perkins EngineAlternator
Benefiting from a choice of leading alternators, the range incorporates the Marelli alternator as standard across three phase models.DCP10
The FG Wilson DCP range allows you to monitor and control your generator set with ease, providing important diagnostic information whilst ensuring your unit operates within safe parameters. FG Wilson DCP digital control panels, provide simple, intuitive menu navigation and control of your generator set operations. Key information is displayed via the LCD screen and LED’s using universally recognised symbols, eliminating the need for complex instructions or language settings.Design Criteria
Prime Rating These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours. Standby Rating These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3). Standard Reference Conditions Note: Standard reference conditions 25°C (77°F) Air Inlet Temp, 100m (328 ft) A.S.L. 30% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2.Single-Source Supplier
Fully prototype tested with certified torsional vibration analysis availableWorld Wide Product Support
FG Wilson manufactures product in the following locations: Northern Ireland • Brazil • China • India • USA With headquarters in Northern Ireland, FG Wilson operates through a Global Dealer Network.Optional Equipment
Exhaust
- Industrial, Residential, Critical Silencers
Alternator
- Upgrade to Leroy Somer Alternator
- Quadrature Droop Kit (AR6)
- Anti-Condensation Heater and Panel Circuitry (AH1)
Control Panels
- PowerWizard 1.1 Control Panel (PWT1.1)
- PowerWizard 1.1+ Control Panel (PWT1.1+)
- PowerWizard 2.1 Control Panel (PWT2.1)
Starting/Charging
- Lead Acid battery (Dry)
General
- Upgrade to Standard Set for "CE" Certification
- EEC Declaration of Conformity
- Narrow, Wide or Skid Base
- Sound attenuated, steel or galvanised enclosure
Standard Equipment
Engine
- Air Cleaner
- Lube oil drain valve
- Engine filled with lubrication oil
- High Coolant Temperature Shutdown
- Low Oil Pressure Shutdown
Cooling
- Package mounted radiator
- Radiator & Cooling Fan
- Coolant Drain Valve
- Fan, Fan drive and battery charging Alternator drive fully guarded to meet EC Machinery Directive
- Cooling System filled with Coolant mix
Exhaust
- Exhaust flange outlet
- Exhaust stub pipe and gasket
Fuel
- 8 Hr Fuel Tank
- Fuel Fittings for Local and Remote Feed
Alternator
- Marelli
- SHUNT Excitation
- IP23 Protection
Control Panel
- DCP-10
Mounting
- Base, Formed Steel with Single wall Fuel Tank
- Certified Base Mounted Lifting Eyes, and Rear Drag Eyelets
- Anti-vibration mounts