Generator Set Specifications
Minimum Rating
50.0 kVA / 40.0 kW
Maximum Rating
55.0 kVA / 44.0 kW
Emissions/Fuel Strategy
Fuel Optimised
50 Hz Prime
50.0 kVA / 40.0 kW
50 Hz Standby
55.0 kVA / 44.0 kW
60 Hz Prime
- / -
60 Hz Standby
Frequency
50 Hz
Speed
1500 RPM
Voltage
240-415 Volts
50 Hz Prime Rating
These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours.
60 Hz Prime Rating
These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3).
50 Hz Standby Rating
Standard reference conditions 25°C (77°F) Air Inlet Temp, 100m (328 ft) A.S.L. 30% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2.
Engine Specifications
Engine Model
Perkins® 1104C-44TG2/3
Bore
105 mm (4.1 in)
Stroke
127 mm (5 in)
Governor Type
Mechanical
Displacement
4.4l (268.5 cu. in)
Compression Ratio
18.2:1
FG Wilson Diesel Engine
Perkins EngineAlternator
Benefiting from a choice of leading alternators, the range incorporates the Marelli alternator as standard across three phase models.DCP-10
The FG Wilson DCP range allows you to monitor and control your generator set with ease, providing important diagnostic information whilst ensuring your unit operates within safe parameters. FG Wilson DCP digital control panels, provide simple, intuitive menu navigation and control of your generator set operations. Key information is displayed via the LCD screen and LED’s using universally recognised symbols, eliminating the need for complex instructions or language settings.Design Criteria
Prime Rating These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours. Standby Rating These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3). Standard Reference Conditions Note: Standard reference conditions 25°C (77°F) Air Inlet Temp, 100m (328 ft) A.S.L. 30% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2.Single-Source Supplier
Fully prototype tested with certified torsional vibration analysis availableWorld Wide Product Support
FG Wilson manufactures product in the following locations: Northern Ireland • Brazil • China • India • USA With headquarters in Northern Ireland, FG Wilson operates through a Global Dealer Network.Optional Equipment
Exhaust
- Industrial, Residential, Critical Silencers
Alternator
- Alternator options including 3 Phase sensing, quadrature droop kit and PMG
- Anti-Condensation Heater and Panel Circuitry (AH1)
Control Panels
- PowerWizard 1.1+ Control Panel (PWT1.1+)
- PowerWizard 2.1 Control Panel (PWT2.1)
Starting/Charging
- Static battery charger with auto boost for lead acid battery
General
- Upgrade to Standard Set for "CE" Certification
- EEC Declaration of Conformity
- Narrow, Wide or Skid Base
- Sound attenuated, steel or galvanised enclosure
Standard Equipment
Engine
- Air Cleaner
- Lube oil drain valve
- Engine filled with lubrication oil
- High Coolant Temperature Shutdown
- Low Oil Pressure Shutdown
- Exhaust stub pipe and gasket
Cooling
- Radiator & Cooling Fan
- Fan,fan drive and battery charging alternator drive fully guarded to meet EC Machinery Directive
- Cooling System filled with Coolant mix
- Coolant drain valve
Exhaust
- Exhaust flange outlet
- Exhaust stub pipe and gasket
Fuel
- 8 Hr Fuel Tank
- Customer connection fuel sockets
Alternator
- Marelli
- SHUNT Excitation
- IP23 Protection
Control Panel
- DCP-10 / PowerWizard 1.1
Mounting
- Base, Formed Steel with Single wall Fuel Tank
- Certified Base Mounted Lifting Eyes, and Rear Drag Eyelets
- Battery Tray and Cables