Generator Set Specifications
| Minimum Rating | 600 kVA / 480 kW | 
| Maximum Rating | 660 kVA / 528 kW | 
| Emissions/Fuel Strategy | Fuel Optimised | 
| 50 Hz Prime | 600 kVA / 480 kW | 
| 50 Hz Standby | 660 kVA / 528 kW | 
| Frequency | 50 Hz | 
| Speed | 1500 RPM | 
| Voltage | 220-415 Volts | 
Minimum Rating
600.0 kVA / 480.0 kW
Maximum Rating
660.0 kVA / 528.0 kW
Emissions/Fuel Strategy
Standard reference conditions 25°C (77°F) Air Inlet Temp, 100m (328 ft) A.S.L. 30% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2.
| Minimum Rating | 600 kVA / 480 kW | 
| Maximum Rating | 660 kVA / 528 kW | 
| Emissions/Fuel Strategy | Fuel Optimised | 
| 50 Hz Prime | 600 kVA / 480 kW | 
| 50 Hz Standby | 660 kVA / 528 kW | 
| Frequency | 50 Hz | 
| Speed | 1500 RPM | 
| Voltage | 220-415 Volts | 
| Engine Model | Perkins® 2806A-E18TAG1A | 
| Bore | 145.0 mm (5.7 in) | 
| Stroke | 183.0mm (7.2 in) | 
| Governor Type | Electronic | 
| Displacement | 18.1l (1104.5 cu. in) | 
| Compression Ratio | 14.5:1 | 
Perkins Engine
Benefiting from a choice of leading alternators, the range incorporates the FG Wilson alternator as standard.
The FG Wilson PowerWizard range of digital control panels, combine straightforward menu navigation with advanced metering and protection technology. They are used in automatic mains failure applications in conjunction with transfer panels. Our PowerWizard range allows you to monitor and control your generator set with ease, whilst ensuring your unit operates within safe parameters and provides important diagnostic information when needed.
Prime Rating These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours. Standby Rating These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3). Standard Reference Conditions Note: Standard reference conditions 25°C (77°F) Air Inlet Temp, 100m (328 ft) A.S.L. 30% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2.
Fully prototype tested with certified torsional vibration analysis available
FG Wilson manufactures product in the following locations: Northern Ireland • Brazil • China • India • USA With headquarters in Northern Ireland, FG Wilson operates through a Global Dealer Network.